Raytron Technical Review RESEARCH ARTICLE WP-07-03

双金属导体接地系统设计

Grounding System Design Using Bimetallic Conductors

RAYTRON Technical Team1

1RAYTRON Group, China

发布日期: March 2026 版本: 1.0
DOI: 10.1000/raytron.WP-07-03

1. Introduction

1.1 Grounding Importance

Diagram placeholder

MEDIA TODO
Figure fig1 Figure 1: Grounding system functions and components
FunctionPurpose
SafetyProtect personnel
Equipment protectionLimit damage
Lightning protectionPath to earth
System referenceVoltage stability

1.2 Why Bimetallic for Grounding

MaterialConductivityCostTheft Risk
CuHighHighHigh
CCSAdequateLowLow
Galvanized steelLowLowLow

2. Grounding System Functions

2.1 Safety Grounding

RequirementStandard
Step voltageIEEE 80 limits
Touch voltageIEEE 80 limits
Ground potential risePer system design

2.2 Fault Current Path

ParameterRequirement
ImpedanceLow enough for fault clearing
Current capacityWithstand fault energy
ReliabilityContinuous path

2.3 Lightning Protection

ComponentFunction
Air terminalsIntercept lightning
Down conductorsConduct to ground
Ground electrodesDissipate to earth

3. Material Selection

3.1 Conductor Options

Diagram placeholder

MEDIA TODO
Figure fig2 Figure 2: Grounding conductor material comparison
MaterialConductivityAmpacityCorrosionTheft
Copper100%HighModerateHigh risk
CCS-21%21%AdequateGoodLow risk
CCS-30%30%BetterGoodLow risk
Galvanized steel8%LowGoodLow risk

3.2 Selection Criteria

ApplicationRecommended
High fault currentCu or CCS-30%
Theft-prone areaCCS
Cost-sensitiveCCS
High-corrosionCCS or Cu

3.3 Equivalent Sizing

For equivalent ampacity:

Cu SizeCCS-21% Equivalent
4/0500 kcmil CCS
2/0350 kcmil CCS
2 AWG4/0 CCS

4. Design Calculations

4.1 Ground Resistance

Typical targets:

InstallationTarget Rg
Substation<1 Ω
Transmission tower10-25 Ω
Industrial5 Ω

4.2 Fault Current Capacity

4.3 Step and Touch Voltage

Must be within limits:

ConditionLimit Formula
Step voltagePer IEEE 80
Touch voltagePer IEEE 80

5. Installation Guidelines

5.1 Conductor Installation

0:00
VIDEO TODO
Video 1: CCS grounding conductor installation procedures
PracticeCCS Guideline
Burial depthPer code (typically 0.5-0.8m)
ConnectionsExothermic preferred
RoutingAvoid sharp bends
ProtectionConduit at crossings

5.2 Connection Methods

MethodCCS Application
Exothermic weldPreferred
Mechanical clampAcceptable
CrimpUse correct dies

5.3 Electrode Installation

TypeInstallation
Ground rodDrive to depth
Ground plateBury horizontal
Ground gridMesh of conductors

6. Maintenance

6.1 Inspection

ActivityFrequency
Visual inspectionAnnually
Resistance testEvery 3-5 years
Connection inspectionAnnually

6.2 Testing

TestMethod
Ground resistanceFall-of-potential
ContinuityPoint-to-point
Current distributionClamp-on

6.3 Repair

IssueRepair Method
Broken conductorExothermic splice
Corroded connectionReplace/clean
High resistanceAdd electrodes

7. Conclusion

7.1 Summary

AdvantageCCS Grounding
Cost50-70% savings vs Cu
Theft deterrenceExcellent
PerformanceAdequate
Service life30+ years

7.2 Recommendation

CCS is recommended for most grounding applications where:

  • Theft is a concern
  • Cost optimization needed
  • Standard fault current capacity adequate

8. References

  1. IEEE 80. (2013). Guide for Safety in AC Substation Grounding.
  2. IEEE 837. (2014). Qualifying Permanent Connections.

FAQ

How does CCS compare to copper for fault current capacity?

CCS-21% has approximately 21% IACS conductivity versus 100% for copper. For equivalent fault current capacity, CCS conductors need to be sized larger (e.g., 4/0 Cu equivalent requires 500 kcmil CCS).

What is the service life of CCS grounding systems?

CCS grounding conductors have a service life of 30+ years when properly installed, with the copper cladding providing corrosion protection similar to solid copper in most soil conditions.

Can CCS be used for substation grounding grids?

Yes, CCS is suitable for substation grounding grids. Size appropriately for fault current capacity and verify that ground resistance meets IEEE 80 requirements for step and touch voltage limits.

What connection methods work best for CCS?

Exothermic welding is the preferred method for underground CCS connections, providing a permanent, low-resistance joint. Mechanical clamps and compression fittings rated for CCS are acceptable for accessible locations.

徐高磊

(Gaolei Xu)

资深材料科学家

资质荣誉

  • 锐创集团 CTO
  • 浙江省高层次人才特殊支持计划青年人才
  • 绍兴市"科技副总"
  • 绍兴市科技特派员
  • 全国有色金属standards化技术委员会重金属分技术委员会(TC243/SC2)委员

国家standards(主要起草人) 查看官方

发明专利 检索专利

专业Section

CCA(CCA)技术 铜包钢(CCS)制造工艺 双金属复合材料 光伏焊带技术 电动汽车电池极耳材料 连续挤压技术

代表性论文

  • 轧制法制造金属层状复合材料的研究与Applications,《铝加工》2008年第3期
  • 铜铝复合带退火工艺的研究
  • 电缆用铜铝复合带制备工艺研究
  • 轧制铜/铝复合带材在退火过程中的界面组织演变

徐高磊先生是有色金属加工Section的知名专家,拥有超过15年的丰富经验。他入选浙江省高层次人才特殊支持计划青年人才。他在双金属复合材料技术开发方面做出了重要贡献,并为中国铜及双金属材料的standards化工作做出了重要贡献。